Computer on Shared Branch Circuit

Engineering laboratory adjacent to offices.
A computer system used by laboratory personnel exhibited intermittent failures and data errors. Typically these would start around 10 a.m. On some days there were no failures.
A power monitor was installed at the panelboard serving the computer system. The monitor was connected, line-to-neutral (Channel A) and neutral-to-ground (Channel B). The recorded line-to-neutral waveforms were relatively undistorted sine waves, which gave no clues as to the source of the line disturbances.
An event summary of the RMS voltage, Figure 1, revealed a pattern of repetitive sags in the RMS voltage, beginning just after 10 a.m. The regular nature of these sags, as well as corresponding swells on the neutral, were made even clearer by increasing the resolution to a few minutes, Figure 2.

 

Dranetz Case Study: Computer on Shared Branch Circuit
Dranetz Case Study: Computer on Shared Branch Circuit

The regular repetition of the voltage sags was a powerful clue, indicating automatic switching of another load on the circuit. The neutral-to-ground waveform, Figure 3, indicated the load was linear.

Dranetz Case Study: Computer on Shared Branch Circuit